skip to content

Tesk TK In Line Pumps

Tesk TK pumps are single-stage vertical in-line centrifugal pumps with the suction and discharge on one line, for HVAC circulation, cooling, boiler feed and booster systems. Nine series cover DN32 to DN200 and up to 81 m head. Prices are for the bareshaft pump. This guide explains the model code, selection, dimensions and prices.

 

 

Power Range

1.1 – 200 kW

2-pole and 4-pole

 

 

Rated Flow

8 – 900 m³/h

DN32 – DN300

 

 

Max Head

81 m

Single stage

 

 

Liquid Temp

−15 to +70 °C

Hot type to +105 °C

 

 

Pressure

PN12 / PN16

PN16 flanges

 

 

Bareshaft pumps

From R5 089

Incl. VAT

Reading the model code

TK65-34/2: DN65 suction and discharge, rated head 34 m, 2-pole motor (2900 rpm). A /4 model uses a 4-pole motor (1450 rpm) for larger flows.

Why an in-line pump?

The in-line design lets the pump drop straight into a horizontal pipe run with no bends, saving space in plant rooms. The pull-up design separates the motor from the pump body so the motor and seal can be serviced without disturbing the pipework.

TK series and prices

SeriesNozzleModelsPowerPrices (bareshaft)
TK32DN3261.1 – 5.5 kWR5 971 – R8 496Shop
TK40DN4071.1 – 7.5 kWR5 089 – R9 914Shop
TK50DN50111.1 – 22 kWR6 440 – R15 329Shop
TK65DN65102.2 – 50 kWR7 267 – R18 097Shop
TK80DN8093 – 30 kWR8 407 – R18 274Shop
TK100DN10092.2 – 30 kWR7 322 – R18 925Shop
TK125DN12585.5 – 37 kWR16 007 – R37 423Shop
TK150DN15071.1 – 45 kWR26 417 – R41 488Shop
TK200DN2001418.5 – 90 kWR49 380 – R84 346Shop

Selecting a TK pump

  1. Flow and pipe size. Choose the series whose nozzle matches your pipe and flow.
  2. Head. For circulation, the head is the friction loss round the loop; for boosting, add static height and required pressure.
  3. Model. Pick the model whose rated point (shown on each product page with performance points) covers your duty.
  4. Motor. Prices are bareshaft — motor and build-up on request.

Operating limits

ItemSpecification
LiquidsThin, clean, non-flammable liquids without solids or fibres
Liquid temperature−15 °C to +70 °C (hot water type to +105 °C)
AmbientUp to +40 °C, altitude up to 1000 m
Working pressurePN12 standard, PN16 high-pressure type
MotorIP55, insulation class F
Impeller / sealStainless steel impeller, Viton mechanical seal

Frequently asked questions

Does the price include a motor?

No, TK prices are for the bareshaft pump. We quote motors and build-up separately.

What does /2 and /4 mean?

2-pole (2900 rpm) or 4-pole (1450 rpm) motor speed.

Can TK pumps handle hot water?

Standard pumps to +70 °C; the hot water type handles up to +105 °C.

Need a circulation or in-line pump sized?

Send us the flow, the head or loop pressure drop, the liquid temperature and the pipe size.

 WhatsApp us on 082 516 2248   Request a quotation